Dynamic Regulation technical specifications:

Topic

Dynamic Regulation

Speed of response

10 seconds

Pre/post fault

Pre-fault

Delivery range

+/-0.015 -0.2 Hz

Deadband (delivery %)

+/-0.015 (0%)

Initial linear range (delivery %)

+/-0.015 -0.2 Hz (100% at +/-0.2Hz)

Knee point

No knee point

Second linear range (delivery %)

n/a

Full delivery point

+/-0.2Hz

Max ramp start

2 seconds

 