Codes

RANC
New circuit within South East England
Type: Develop new circuits
Status: Scoping
Boundaries:
Region: South Wales and South England
This project is currently required to enable the development of a robust and reliable offshore network connection and will be reappraised in the detailed design stage.
NOA 2021/22 Refresh Recommendation:
Enabling works
RHM1
225 MVAr MSCs at Rye House
Type: Upgrade existing circuits
Status: Strategic Optioneering
Boundaries: EC5E; LE1
Region: South Wales and South England
One new 225 MVAr switched capacitors (MSCs) at Rye House would provide voltage support through East Anglia and North London as system flows increase in future.
NOA 2021/22 Refresh Recommendation:
Proceed - Critical
RHM2
225 MVAr MSCs at Rye House
Type: Upgrade existing circuits
Status: Strategic Optioneering
Boundaries: EC5E; LE1
Region: South Wales and South England
One new 225 MVAr switched capacitors (MSCs) at Rye House would provide voltage support through East Anglia and North London as system flows increase in future.
NOA 2021/22 Refresh Recommendation:
Proceed - Critical
RTRE
Reconductor remainder of Rayleigh to Tilbury circuit
Type: Upgrade existing circuits
Status: Construction
Boundaries: LE1; SC1Rev
Region:
Replace the conductors on the remaining sections of the Rayleigh to Tilbury circuit, which have not recently been reconductored with higher-rated conductors. These would increase the circuit’s thermal rating.
NOA 2021/22 Refresh Recommendation:
Proceed - Critical
SCD1
New Offshore HVDC link between Suffolk and Kent option 1
Type: Develop new circuits
Status: Design/development and consenting
Boundaries: EC5E; EC5I; LE1; SC1.5Rev; SC1Rev; SC2Rev; SC3Rev
Region: South Wales and South England
Construct a new offshore 2 GW HVDC circuit between Suffolk and Kent.
NOA 2021/22 Refresh Recommendation:
HND essential option
SEEU
Reactive compensation protective switching scheme
Type: Operational and reduced-build options
Status: Strategic Optioneering
Boundaries: SC2; SC2Rev
Region:
Provide a new communications system, and other equipment, to allow existing reactive equipment to be switched in or out of service very quickly following transmission system faults. This would allow better control of system voltages following faults.
NOA 2021/22 Refresh Recommendation:
Proceed - Critical
SER1
Elstree to Sundon reconductoring
Type: Upgrade existing circuits
Status: Strategic Optioneering
Boundaries: LE1; SC1Rev
Region:
Replace the conductors from Elstree to Sundon circuit 1 with higher-rated conductors to increase their thermal rating.
NOA 2021/22 Refresh Recommendation:
HND essential option
SER2
Elstree to Sundon 2 circuit turn-in and reconductoring
Type: Upgrade existing circuits
Status: Strategic Optioneering
Boundaries: EC5E; LE1; SC1Rev
Region: South Wales and South England
Turn-in the Elstree to Sundon circuit 2, which currently passes the Elstree 400 kV substation, to connect to it and replace the conductor with a higher-rated conductor. This would ensure better load flow sharing and increase their thermal rating.
NOA 2021/22 Refresh Recommendation:
HND essential option
SGRE
Reconductor Grendon to Sundon 400kV double circuit
Type: Upgrade existing circuits
Status: Strategic Optioneering
Boundaries: LE1;
Region: South Wales and South England
Replace the conductors on the existing circuit between Grendon and Sundon with higher capacity conductors
NOA 2021/22 Refresh Recommendation:
Proceed - Critical
SHNS
Upgrade substation in the south Humber area
Type: Build a new substation or reconfiguring an existing substation
Status: Design/development and consenting
Boundaries: B6I; B7aI; B8; B9
Region: North England
Substation upgrade of the 400 kV South Humber substation equipment.
NOA 2021/22 Refresh Recommendation:
HND essential option