Regional drivers
The connection of large amounts of new generation, most of which is intermittent renewables, in Scotland and the north will cause overloading in the northern transmission network unless appropriate reinforcements are in place. Future power transfer requirements could be more than double compared to what they are today in some scenarios.
All four scenarios suggest growth in low-carbon and renewable generation, in addition to new storage and interconnector developments. The connected fossil fuel generation could see sustained decline in all but the Steady Progression scenario., but would not be phased out in the region until at least 2040. Presently, most of the northern transmission network is oriented for north-south power flows with connections for demand and generation along the way.
At times of high wind generation, the power flow will mostly be from north to south, with power coming from both internal boundary generation and generation further north in Scotland.
When most of this area and Scotland is generating power, the transmission network can be highly overloaded. The loss of one of the north-to-south routes can have a highly undesirable impact on the remaining circuits.
As the potential future requirement to transfer more power from Scotland to England increases, B7a is likely to reach its capability limit and needs network reinforcement. The potential future restrictions to be overcome across B7a are summarised:
At high power transfer, thermal limitations occur on a number of circuits within the north east 275kV ring.
Limitation on power transfer from Cumbria to Lancashire (boundary B7a) occurs due to thermal limitation at Padiham–Penwortham circuit.
The need for network reinforcement to address the abovementioned potential capability issues will be evaluated in the NOA 2021/22 CBA.
Gross demand in the North of England in expected to increase to a total of up to 11GW by 2030, generation in the region is already double that figure today, and will increase by an additional 5GW by 2020. The North of England is a heavily power-exporting region and must also manage power flows from Scotland to the demand centres in the Midlands and South.
All four scenarios show a steady increase in the gross demand of the region that is outstrips the increase in local generation for all but the Leading the Way scenario. There are stark differences seen in the range of local generation under the four scenarios, from 5 – 10 GW is expected by 2050, up from 2.8GW today. More local generation will mean that less of the North-South power flows that travel through this region will be absorbed by demand.
The highly variable nature of power flows in the north presents challenges for voltage management, and therefore automatic reactive power control switching is utilised. This helps to manage the significant voltage drop due to reactive power demands which arise at times of high levels of power flow on long circuits.
Operational reactive switching solutions are also used to manage light loading conditions when the voltage can rise to unacceptable levels. The high concentration of large conventional generators around Humber and South Yorkshire means that system configuration can be limited by high fault levels. Therefore, some potential network capability restrictions in the north can be due to the inability to configure the network as desired due to fault level concerns.
The need for network reinforcement to address the abovementioned potential capability issues will be evaluated in the NOA 2021/22 CBA.